Inspection Status: Approved
Inspection History: FIREWALL/FIREBARRIER/FIRESTOP
| Date |
Description |
Inspector |
Results |
Comments |
| 09/03/2021 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Approved |
Approved. Third floor draft stops on Level #3. |
| 08/30/2021 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
1036, 2036, 3036, 4036, 1044. Partial. Second floor only. OK to install drywall soffit areas |
| 08/26/2021 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Not ready for Inspection |
Not ready. Contractor cancelled. |
| 08/17/2021 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Denied |
DE ( missing fire caulking in many places throughout 2nd floor) |
| 08/16/2021 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Cancelled |
Cancelled, unable to meet at site |
| 07/30/2021 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
Partial, 1st floor continuous 1Hr horizontal assembly for North side rooms 1-4 and South side corner room. Partial, 2nd floor North side rooms and South side rooms 2-5 for draft stops. |
| 07/21/2021 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
PARTIAL, ABOVE CEILING FIRE ASSEMBLIES AND DRAFT STOPS INSTALLED FIRST FLOOR, South units. |
| 07/16/2021 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
Partial, Northside firewalls and draft stops |
| 06/22/2021 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
Partial. Level #2; Room Units and corridors. |
| 05/26/2021 |
FIREWALL/FIREBARRIER/FIRESTOP |
|
Partial Approval |
Partial. Missing fire blocking between units above ceiling. Missing draft stopping every 10 feet. |