Permit: T20CM00360

Parcel: 117062070


Addresses:

127 S 5TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/20/2021 ELECTRIC - INTERMEDIATE Approved
04/12/2021 ELECTRIC - INTERMEDIATE Approved Partial. Level #7: Meters and room panels at 701, 702, 703. 704, 705. 706. 707, 708. 709, 710, 711. 712, 713. 714, 715, 716. Ok to energize meters and panels.

Clearance. Code, ECO
04/06/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #6; meters and room panels for Room Units 601; 602. 603; 604,; 605; 606; 607; 608; 609; 610; 611, 612; 613; 614; 615; 616. Ok to energize meters and panels.

Clearance, Code: ECO
04/05/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #7; meters and room panels at 701-716. No clearance required at this time.
04/05/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #3; Ok to energize meters and panels in Room Units 301; 302, 303; 304; 305; 306; 307; 308; 309; 310; 311; 312; 313; 314; 315; 316.
Level #4; Ok to energize meters and panels in Room Units 401; 402; 403; 404; 405; 406; 407; 408; 409; 410; 411; 412; 413; 414; 415; 416.
Level #5; Ok to energize meters and panels in Room Units 501; 502; 503; 504; 505; 506; 507; 508; 509; 510; 511; 512; 513; 514; 515; 516.

Clearance; Code: ECO
04/02/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #7; meters and room panels are labeled. No clearance required at this time: Room Units 701-716.
04/01/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #3; meters and room panels 301; 302; 303; 304; 305; 306; 307; 308; 309; 310; 311; 312; 313; 314; 315; 316. Ok to energize. Level #4; meters and room panels 401; 402; 403; 404; 405; 406; 407; 408; 409; 410; 411; 412; 413; 414; 415; 416. Ok to energize.
03/31/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #6; Meters and Room Unit panels; 601-616. Meters and panels are labeled; no clearance required at this.
03/30/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #5; Meters and Room Units panels are labeled. Nor clearance required at this time; Room Units 501-516. Level #2; Meters and Room panels; Ok to energize Room Units 201; 202; 203; 204; 205; 206; 207; 208; 209; 210; 211; 212; 213; 214; 215 216. Ok to energize meters and panels.
03/26/2021 ELECTRIC - INTERMEDIATE Not ready for Inspection
03/25/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #4; Room panels and meters at Room Units 401-416.
No clearance required at this time; buss duct and transformer are not in place.
03/24/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #3; Meter sets and Room panels labeled. No clearance for power needed at this time.
03/23/2021 ELECTRIC - INTERMEDIATE Partial Approval . Partial. Level #2; Room panels and room meters labeled. Not to be energized until buss duct and transformer are installed.
03/22/2021 ELECTRIC - INTERMEDIATE Not ready for Inspection Not ready. Meters are not labeled; buss duct not installed.
03/18/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Information only. Meeting with TEP to discuss metering inspections.
03/03/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Electric in walls and ceilings.
02/24/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #1; Lobby areas and restrooms; electric in walls.
02/12/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #7 Corridor, walls and ceilings
02/03/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #7; Room Units 710-714.
01/29/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #7; Room Units 701; 702; 716. Ensure electric putty packs are properly placed in walls as per NEC.
01/25/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #7; Room Units 703; 704
01/22/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #7; Room Units 705; 706; 707; 708; 709. Ensure fire putty packs are installed in laundry areas.
01/21/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Electric room, SES 480Y/277V; 3 phase 4W; 2000 Amps. Ok to energize system. Please resubmit for clearance

Clearance; Code: ECO
01/19/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Electric room: SES 480Y/277V, 3PH 4, 2000 Amps. Ok to energize system and set meter. Please submit to TEP
01/13/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #6; Room Units 601; 602; 603; 604; 616
01/11/2021 ELECTRIC - INTERMEDIATE Not ready for Inspection Not ready. Panels not in place. Room Units 601; 602; 603; 616.
01/07/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. SES System, Bus Duct cabinet, meter cabinet. Ok to energize system when TEP clears meter cabinet. No clearance required at this time.
01/05/2021 ELECTRIC - INTERMEDIATE Not ready for Inspection Not ready. Level #6; Room Units 601; 602; 603; 604; 607; 611; 612; 616 not ready.
12/31/2020 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #6; Room Units 605; 606; 609: 610; 613; 614; 615. Ensure putty packs are properly place as per code require.
12/16/2020 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #5; Room Units 501; 502; 503; 504; 505; 515. Ensure penetrations between units are properly fire caulked and putty packs are properly placed between outlets.
12/14/2020 ELECTRIC - INTERMEDIATE Partial Approval PARTIAL
12/11/2020 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #5; Room Units 507; 508; 509; 510; 511; 512; 513.
12/10/2020 ELECTRIC - INTERMEDIATE Cancelled Canceled by contractor.
11/30/2020 ELECTRIC - INTERMEDIATE Partial Approval Partial. Units 401, 402, 410, 411, 413, 414.
11/25/2020 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level 4, units 403 thru 409.
11/13/2020 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #2; Room Units 201-216.
11/04/2020 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #3; 16 Room Units; Ok to insulate and cover walls.
11/02/2020 ELECTRIC - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled
10/30/2020 ELECTRIC - INTERMEDIATE Not ready for Inspection Not ready. Contractor cancelled, will reschedule for 3 November.
09/01/2020 ELECTRIC - INTERMEDIATE Partial Approval Partial. Conduit lines (4” at 6 each) for SES service; approximately 75’. Ok to cover progress areas.