Permit: T20CM00360

Parcel: 117062070


Addresses:

127 S 5TH AV

Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Date Description Inspector Results Comments
06/01/2021 BUILDING - PROGRESS Approved Approved
05/27/2021 BUILDING - PROGRESS Partial Approval
05/26/2021 BUILDING - PROGRESS Partial Approval Partial. Level #5 and #6; Room Units 510-516; 601-616; Final room inspections.
05/25/2021 BUILDING - PROGRESS Partial Approval Partial. Level #2; Room Units inspections at 201 - 216.
05/24/2021 BUILDING - PROGRESS Partial Approval Partial. Final Room Unit inspections on Level #4: 401-416
05/20/2021 BUILDING - PROGRESS Partial Approval PARTIAL PERMIT UPDATE
05/19/2021 BUILDING - PROGRESS Not ready for Inspection Not ready. Level #4 Room Units. Permit up date scheduled for 20 May.
05/18/2021 BUILDING - PROGRESS Not ready for Inspection Not ready. Levels #3; 4; 5: Room Units not ready for inspection.
05/17/2021 BUILDING - PROGRESS Partial Approval Partial. Room check: Level #3: 302; patch ceiling at West wall of bedroom. Rooms 314 and 315 missing Braille room numbers. 313; bathroom exhaust only works when bathroom light is on.
Level#4: 403; entry lights do not work; lights above sink, bulb does not work. 404, disposal switch will not turn on/off. 405; breaker #8 will not set to on position. 416; weather strip frame of door to balcony.