Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T20CM00312
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2022 | ELECTRIC - UNDERGROUND | Approved | Approved | |
| 05/18/2021 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. From south chiller wall to transformer pad. Three light poles on south west corner of building. | |
| 05/12/2021 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. North side parking light pole to middle light pole. | |
| 01/28/2021 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. Electric conduits, 4 each at 1 1/2” from Southwest corner to Riser: approximately 60’. Ok to place tape and cover progress area. | |
| 01/25/2021 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. Electric conduits (3” and 3/4”) at Packers Section south to riser: approximately 72’. Ok to cover progress areas. | |
| 01/21/2021 | ELECTRIC - UNDERGROUND | Cancelled | IVRS - AP canceled | |
| 01/20/2021 | ELECTRIC - UNDERGROUND | Partial Approval | PARTIAL UNDERGOUND CONDUIT RN FOR SOLAR. FROM EXISTING J2 TO SOUTH WEST CORNER OF GREEN BAY BUILDING | |
| 11/05/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. From southwest transformer to Green Bay electrical room. | |
| 10/13/2020 | ELECTRIC - UNDERGROUND | Partial Approval | ||
| 07/01/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. 3/0 copper, continuous in footing ufer to connect all services. | |
| 06/11/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. Column 13- gridline AA to DD. | |
| 06/09/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. Column 12- gridlines BB thru JJ. | |
| 06/05/2020 | ELECTRIC - UNDERGROUND | Not ready for Inspection | Not ready. | |
| 06/01/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. Ufer from Electric Room #108 to Electric Room #112; GL: 1-6. Ok to cover progress areas. | |
| 05/26/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Electric. Partial. From FF-13 to OO-14 to electrical room #3. From electrical room #3 to WW-14. This line will be going to the TEP transformer. | |
| 05/21/2020 | ELECTRIC - UNDERGROUND | Not ready for Inspection | Not ready. | |
| 05/12/2020 | ELECTRIC - UNDERGROUND | Partial Approval | Partial. From transformer to electrical room #4. |