Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2020 | FIRE - ALARM FINAL | Approved | ||
| 12/23/2020 | FIRE - ALARM FINAL | Denied | Air flow needs to shut down when duct smoke in costume storage room is activated. A re-inspection fe wil be added |
|
| 12/22/2020 | FIRE - ALARM FINAL | Denied | Duct smoke in ballet room not functioning Duct smoke in music rom office mislabled Duct smoke in prop storage room not functioning |
|
| 08/14/2020 | FIRE - ALARM FINAL | Partial Approval | For 3D art and 2D art rooms only verify total system compliance before final |