Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T19FC00582
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2019 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | ||
| 09/09/2019 | FIRE SPKLR - UG, PIPING, HYDRO | Denied | Pressure gauge at 175 psi. Test needs to be at 200 psi for 2 hours or more. Reschedule when pumped at 200 psi. | |
| 08/09/2019 | FIRE SPKLR - UG, PIPING, HYDRO | Not ready for Inspection | Saw UG line it is okay. Okay to test from backflow to pipe connection. Water leak currently to the street main. Water is aware of the issue. |