Inspection Status: Approved
Inspection History: FIRE PUMP - FINAL
Permit Number - T19FC00280
Inspection Description - FIRE PUMP - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2020 | FIRE PUMP - FINAL | Approved | ||
| 05/18/2020 | FIRE PUMP - FINAL | Partial Approval | Fire pump room needs to have ventilation Need fire pump room and test header signs to be in place Need to flow the standpipes |
|
| 03/20/2020 | FIRE PUMP - FINAL | Partial Approval | Early morning inspection for the fire pump. Tested pump but the emergency power has a hole in the radiator and we cannot run all auto start stops until the radiator is complete. Electric and fire alarm signals were ok. |