Permit: T19FC00280

Parcel: 11712099A


Addresses:

20 S STONE AV


Inspection Status: Approved

Inspection History: FIRE PUMP - FINAL

Permit Number - T19FC00280

Inspection Description - FIRE PUMP - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2020 FIRE PUMP - FINAL Approved
05/18/2020 FIRE PUMP - FINAL Partial Approval Fire pump room needs to have ventilation
Need fire pump room and test header signs to be in place
Need to flow the standpipes
03/20/2020 FIRE PUMP - FINAL Partial Approval Early morning inspection for the fire pump. Tested pump but the emergency power has a hole in the radiator and we cannot run all auto start stops until the radiator is complete. Electric and fire alarm signals were ok.