Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/20/2019 |
FIRE - ALARM FINAL |
|
Approved |
|
| 10/25/2019 |
FIRE - ALARM FINAL |
|
Partial Approval |
Need asbuilt drawings and fees to be piad prior to closing out this permit |
| 08/23/2019 |
FIRE - ALARM FINAL |
|
Partial Approval |
Tested the fire alarm system, manual pull stations, smokes and duct smokes. Need to add outside weather proof notification devices. Need RED lock outs on the panels and disconnecting measn labeled in the FACP and Power supplies. Submit As-built fire alarm drawings |