Permit: T19CM06141

Parcel: 14108521E

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/07/2019 MECHANICAL - FINAL Approved REVIEW OF AIR BALANCE REPORT COMPLETED
10/03/2019 MECHANICAL - FINAL Partial Approval 50" Exhaust fan pulling 21,000 CFM’s from warehouse. 2-22" Patterson fans with tube ducts 5,570 CFM’s per fan utilizing interior airflow. Final pending submitted air balance report, and approval from Robert Sherry.
08/26/2019 MECHANICAL - FINAL Prior to Final Inspectn AIR BALANCE REPORT REQUIRED