Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM04691
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/06/2021 | FIRE - FINAL | Approved | ||
07/01/2020 | FIRE - FINAL | Prior to Final Inspectn | FIRE ALARM MONITORING PERMIT REQUIRED PRIOR TO A COFO BEING ISSUED. | |
05/19/2020 | FIRE - FINAL | Partial Approval | 1. Ok for TCO for full operation. 2. Need permit for monitoring. 3. Install keys in Knox box. |
|
04/09/2020 | FIRE - FINAL | Partial Approval | 1. Prior to C of O will need the following. -syncing of horn/strobes in retail space. -2 EM lights fixed. -FDC sign. -FDC Know caps. -Permit for monitoring (UL Listed Company). -Riser sign on door. -Add permanent exterior address numbers. -install keys in both Knox boxes 2. Ok for TCO for stocking and fixtures. |