Permit: T19CM03849

Parcel: 140182090


Addresses:

5161 S FREMONT DR

Inspection Status: Not Ready

Inspection History: COT - LCBU - Framing

Date Description Inspector Results Comments
10/27/2022 COT - LCBU - Framing Not Ready
04/09/2026 COT - LCBU - Framing Passed 04/09/2026
Corrections made to prior inspections, verified hangers, anchor bolts and shot pins per schedule.
07/28/2025 COT - LCBU - Framing Re-inspection required 7/28/2025 provide 2 layers of vapor barrier per t1-11.
11/15/2024 COT - LCBU - Framing Re-inspection required 11/15/24: Anchor bolt spacing greater than 32" o.c throughout, anchor bolts required 12" from edge of sill plate, shot pins required 6" from edge of sill plate. Shot pins required 48" o.c, damaged roof joist must be replaced, anchor bolts at ledger required per plan.
11/22/2024 COT - LCBU - Framing Partial Pass 11/15/24: Anchor bolt spacing greater than 32" o.c throughout, anchor bolts required 12" from edge of sill plate, shot pins required 6" from edge of sill plate. Shot pins required 48" o.c, damaged roof joist must be replaced, anchor bolts at ledger required per plan.
11/22/24: partial pass for roof ok to proceed with drying-in. Anchor bolts must be properly fastened (will check at intermediate), hangers must be properly installed ( removed to show anchor bolts at ledger).