Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2020 | FIRE - FINAL | Approved | -had them remove mags from mag lock doors, main exit. they were not interconnected to alarm or had the push to exit button. they will contact us if they decide to reinstall mag hardware. | |
| 01/21/2020 | FIRE - FINAL | Partial Approval | -Need to final sprinkler monitoring FA -Post "not a door" sign or remove door knob to NW door. -Relocated interior FDC sign to exterior gate. Remove arrow from sign. Shall be mounted on the gate. -Add FACP sign to interior door. -Install knox FDC plugs. Flush was witnessed. Female swivel threads are damaged. Unable to install. Openings were covered with duck tape to prevent debris from entering. -Taped head in closet next to riser room. |
|
| 12/06/2019 | FIRE - FINAL | Partial Approval | APPROVED TO OBTAIN TCO FOR FULL OCCUPANCY. -mount extinguishers. -order/mount knox box next to FDC gate. provide master keys and keys to gates. -need sprinkler monitoring. -remove exit sign, N. exit, warehouse. -add "not a door" or remove door hardware from NW door, warehouse, that is not a door. -mount address numbers on bldg. -need to research exit door, swing, etc... on main S. exit, half door. -FDC sign on gate. -Order knox FDC plugs for connections. -Move FDC gate located on N. side of connections to provide space for connecting hose lines. -flush FDC, tfd to witness. knox plugs must be on site. |