Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM03517
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2019 | FIRE - FINAL | Approved | ||
11/27/2019 | FIRE - FINAL | Partial Approval | APPROVED TO OBTAIN TCO FOR FULL OCCUPANCY ON FIRST FLOOR. Outstanding items: -Painted head SE bathroom. -Need to test and provide report for emergency responder radio coverage. -FDC sign not FCP sign. -Two way communication signage next to each call station. -Mount extinguishers on 2nd and 3rd floors. -Need elevator keys placed in elevator knox box. -Lockout fire bell. -Updated/permanent stairwell signs need to be mounted. -EM lighting needed in electrical rooms. |
|
11/13/2019 | FIRE - FINAL | Partial Approval | -OK to obtain TCO -complete sprinkler and alarm inspections -provide key to front door and riser room -provide elevator inspection paperwork |