Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T19CM03517

Parcel: 117033190


Addresses:

434 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T19CM03517

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2019 FIRE - ALARM FINAL Approved
11/27/2019 FIRE - ALARM FINAL Partial Approval Acceptance test conducted. Elevator in compliance.
List of outstanding items:
-Obtain permit for monitoring.
-Need as builts approved and all fees paid.
-Provide locking/secure box around transformer plug from teleguard communicator to outlet.
-Tamper switch on 2nd floor reporting as water flow. This was resolved and retested while on site.
-Work room on plans wants horn/strobe in center of room.
-Replace strobe only in NE office with horn/strobe as indicated on plans.
-Need to test comm failures.
-Provide record of completion.
-Update TFD fire dispatch phone number with central station.
-Two way communication on 3rd floor not working.
11/13/2019 FIRE - ALARM FINAL Partial Approval -submit as-buillt plans
-panel shall show no trouble signals
-need to test elevator 2-way emergency call buttons.