Inspection History Details
Permit: T19CM03359
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2019 | ELECTRIC - RECONNECT | Approved | PV Line side Tap in Existing 277/480V, 1200AMP SES From new fused 400AMP PV Utility Disconnect. 2 sets of Parallel Copper Conductors #250Kcmil , #1AWG Neutral, #1AWG Grnd. Verbal Clearance sent to TEP (RECN) @ 2:15AM. Upon arrival collected a check for $165 for after hours inspection. |