Permit: T19CM02818

Parcel: 117120310

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T19CM02818

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/03/2020 FIRE - FINAL Approved
03/04/2020 FIRE - FINAL Denied -Need to obtain and install 1 fire extinguisher
-Add suite numbers to the front and back door in 3" stroke
-Interior front door needs sign "This door to remain unlocked while building is occupied"
-Key for the KNOX Box
-Building has EST fire alarm - fire alarm permit and plans required also need fire alarm final prior to fire final
-Pay re-inspection fees prior to calling the fire final back in
-Replace missing escutcheon in cleaning room