Inspection History Details
Inspection Status: Passed
Inspection History: COT - HCBU - Building Above Ceiling
Permit Number - T19CM01996
Inspection Description - COT - HCBU - Building Above Ceiling
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/05/2019 | COT - HCBU - Building Above Ceiling | JBURGE | Approved | Entered by DMERANZ1 - Phase III complete. Ok to set ceiling tiles |
11/25/2019 | COT - HCBU - Building Above Ceiling | JBURGE | Partial Approval | Entered by DMERANZ1 - Level #2; Restrooms #22103A; 22103B; corridor #22182. Ok to place ceiling tiles |
10/11/2019 | COT - HCBU - Building Above Ceiling | JBURGE | Partial Approval | Entered by DMERANZ1 - Administration area offices of Phase I, Ok to set ceiling tiles. |
08/27/2019 | COT - HCBU - Building Above Ceiling | JBURGE | Partial Approval | Entered by DMERANZ1 - Dialysis public corridor, Ok to set ceiling tiles in progress areas. |
07/02/2019 | COT - HCBU - Building Above Ceiling | JBURGE | Partial Approval | Entered by DMERANZ1 - Dialysis corridor; Room #22225; 22226: ensure all penetrations are Fire caulked; all "J" boxes are closed; fire alarm boxes need to be secured; all air duct joints are air sealed. |