Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T19CM01916
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/10/2020 | FIRE - FINAL | Approved | ||
02/07/2020 | FIRE - FINAL | Partial Approval | emergency lighting in halls required Fire sprinkler still due for 5 year Address needs to meet code requirements Gate to be installed so we can confirm proper operation |
|
01/10/2020 | FIRE - FINAL | Partial Approval | OK FOR TCO TO OCCUPY THE SECOND PHASE Need to supply documentation for annual and 5 year for the fire sprinkler system add fire extinguisher to the back class rooms Replace the water flow and add a tamper switch that can be monitored Remove the old fire alarm and components in the basemenet assembly areas need to have the occupant load signs installed Need FACP and RISER ROOM signs Replace Supra with new KNOX Box Address required 12" Front gate shall be modified so that it meets the code requirements Add an exit sign in from conference room Need to verify emergency and exit lights no electrician onsite See fire alarm and fire sprinkler notes Pay re-inspection fees prior to calling final back in |
|
12/11/2019 | FIRE - FINAL | Partial Approval | 1. Ok for TCO to stock and occupy for Administration. | |
11/26/2019 | FIRE - FINAL | Partial Approval | TCO okay to install furniture. | |
11/22/2019 | FIRE - FINAL | Denied | Work not complete |