Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T19CM01916
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/11/2020 | BUILDING - FINAL | Approved | ||
03/09/2020 | BUILDING - FINAL | Partial Approval | Pending other inspections. | |
02/12/2020 | BUILDING - FINAL | Partial Approval | PENDING AIR BALANCE REPORT, RIGHT OF WAY FINAL, AND FIRE FINAL | |
02/04/2020 | BUILDING - FINAL | Denied | 1- The plaster traps have been installed incorrectly due the trap arm height. 2- Shall secure the HWR pump and expansion tank at the water heater. |
|
01/09/2020 | BUILDING - FINAL | Partial Approval | Ok to make application for Temporary Certificate of Occupancy. | |
12/09/2019 | BUILDING - FINAL | Partial Approval | Ok for TCO for office personnel to occupy, pending fire and engineering. Contractor will submit a floor plan showing distance of means of egress and construction separation to general public. | |
11/25/2019 | BUILDING - FINAL | Not ready for Inspection | ||
11/22/2019 | BUILDING - FINAL | Partial Approval | Office area on south side ok for TCO. |