Permit: T19CM01742

Parcel: 11709035H


Addresses:

1004 S RUSSELL AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/24/2019 PLUMBING - ROUGH, SOIL Approved
05/20/2019 PLUMBING - ROUGH, SOIL Denied 1- Shall provide a minimum 2 times the pipe diameter for the trap arm distance at tub waste. Reference section 909.3 2018 IPC
2- Re test system.
05/17/2019 PLUMBING - ROUGH, SOIL Denied 1- Shall locate the outlet of the vent to the tub above the centerline of the drain.
Reference section 905.3 2018 IPC
2- Retest the system.