Permit: T19CM01742

Parcel: 11709035H


Addresses:

1004 S RUSSELL AV

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
07/12/2019 REINFORCED MASONRY PRE-GROUT Approved
06/19/2019 REINFORCED MASONRY PRE-GROUT Not ready for Inspection here for second lift, no ladder or safe scaffolding set up to inspect. Left message with Francisco the framer about needing access at time of inspection.
06/07/2019 REINFORCED MASONRY PRE-GROUT Partial Approval first lift OK to grout.
06/04/2019 REINFORCED MASONRY PRE-GROUT Not ready for Inspection no drawings on site nor were they on pro. Need to see detail on openings as currently the rebar on either side of doors and windows does not tie into footings. This may need an engineering fix before we can approve.
05/13/2019 REINFORCED MASONRY PRE-GROUT Not ready for Inspection