Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2019 | MECHANICAL - FINAL | Partial Approval | pending air balance report to Bob Sherry | |
| 05/02/2019 | MECHANICAL - FINAL | Approved | REVIEW OF AIR BALANCE REPORT COMPLETED | |
| 04/30/2019 | MECHANICAL - FINAL | Partial Approval | Pending fire approval Women’s ADA water closet may not exceed 18 inches from wall Install ADA signs at bathrooms 5 foot center Provide air balance report and water chlorinator report to Bob Sherry an office |