Permit: T19CM00883

Parcel: 11203271B

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/06/2019 PLUMBING - FINAL Denied 1- Shall provide (3) sheet metal screws per joint on the water heater flu vent and draft collar and remove the mechanical tape around the dbl wall flu vent.
2- Shall provide a gas bond on the system.
3- Shall extend and terminate the wall heaterflu vent (3) feet above the cooler.
4- Shall extend and terminate the water heater T & P drain to daylight.
5- Shall secure the gas line drop to the wall furnace.
02/06/2019 PLUMBING - FINAL Approved All corrections have been made. Clear gas meter Verbal clearance called in at 2:53pm