Permit: T19CM00216

Parcel: 119045970


Addresses:

3714 S LUNDY AV

Inspection Status: Passed

Inspection History: COT - RSBU - Roof Nailing 

Date Description Inspector Results Comments
01/16/2020 COT - RSBU - Roof Nailing  TVALENCIA Approved Entered by DMERANZ1 -
07/30/2019 COT - RSBU - Roof Nailing  MHASSAN Partial Approval Entered by DMERANZ1 - roof overhang is not per drawing and is 3 feet on south side of house which is now making it only 4 feet to the property line. 2 feet is maximum unless designed that way, also anything within 5 feet of property line will need a fire rating. There are still issues with the homemade trusses not being per drawing. Please revise drawings or build per drawing. Add anchors into bottom plate on south wall. Nails were added in the sheathing, however drywall screws are still in the sheathing. Either seal the screwheads so they will not rust through the stucco later or remove them leaving the correct amount of nailing per drawing. OK to cover roof with the exception that the overhang on southside will need to be addressed.
06/25/2019 COT - RSBU - Roof Nailing  RCAMACHO Denied Entered by DMERANZ1 - Provide 2 x 8 ridge per plan Top plate splices at least 48” per note 7 Provide 8 D common nails 6” of at edges 12” in field per plywood note 3. Drywall screws may not be used Provide 3 hole bird board blocking for diaphragm nailing per detail 1 What is fix for splice at ridge board. Stopped inspection