Inspection History Details
Permit: T19CM00016
Inspection Status: Approved
Inspection History: OUTDOOR LIGHTING FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2019 | OUTDOOR LIGHTING FINAL | Approved | Interconnection from 500AMP PV Utility, Disconnect to Existing 2000 AMP 277/480V SES. 2 Parallel sets of 3-#400MCM AL Conductors, 1- #1/0 AL Grnd, in 2-3” RMC Conduits. Sent verbal Clearance To TEP @ 10:50AM (RECN/DGC). Upon arrival collected check for after hours inspection, for $165. |