Permit: T19CM00016


Addresses:

5801 S DEL MORAL BL

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
08/17/2019 ELECTRIC - PROGRESS Approved Interconnection from 500AMP PV Utility, Disconnect to Existing 2000 AMP 277/480V SES.
2 Parallel sets of 3-#400MCM AL Conductors, 1- #1/0 AL Grnd, in 2-3” RMC Conduits.
Sent verbal Clearance To TEP @ 10:50AM (RECN/DGC).
Upon arrival collected check for after hours inspection, for $165.
08/16/2019 ELECTRIC - PROGRESS Cancelled this inspection is an after hours inspection on Saturday the 17th David Muniz will be doing it.