10/30/2018 SIGN SITE REVIEW Continued Contractor submitted special inspection form for review
10/30/2018 SIGN SITE REVIEW Approved
10/25/2018 SIGN SITE REVIEW Partial Approval RE: permit T18OT01093
Site: Caterpillar/ 875 W Cushing St
Date: 10/25/18
For: 2 wall signs

Engineering received/ approved 10/25/18 for wall signage attachments.

All corrections made from prior review.

To release permit - need special inspection form signed/sealed from engineer to designate special inspection for attachment and qualified special inspector.

Partial approval. - HT
10/24/2018 SIGN SITE REVIEW Continued Contractor has been in touch - awaiting engineering for larger lettered wall sign above entry to building. Need to review attachments to building via sealed engineered plans/calcs.
10/17/2018 SIGN SITE REVIEW Partial Approval RE: wall sign review
For: 875 W Cushing / Caterpillar
Permit: T18OT01093
Reviewer: H. Thrall
Date: 10/17/18 via emailed drawings from contractor

Zoning of I-1 for sign allowances for site.

Proposal: two wall signs.

1) Provide engineering for attachments for 124 square foot wall sign, as signage is greater than 30' off ground 7A.4.5.C. Ensure drawings match engineering. (Check which sign this is shown as on site plan drawing between the two.)

2) clearly label shut off switch for each sign (NEC 600).

3) per Outdoor Lighting Code 501.3.2, note interior illuminated sign color temperature shall not exceed 4400k.

Further review comments may be forthcoming.