Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date |
Description |
Inspector |
Results |
Comments |
| 06/19/2018 |
INSP - INITIAL CODE ENFORCMENT |
|
Approved |
THE MAIN SERVICE DISCONNECT (ALL IN ONE (A)) HAS NON CODE COMPLIANT MODIFICATIONS DONE TO THE UNIT. ALL OF THE INTERIOR COMPONENTS HAVE BEEN REMOVED WHICH IS A VIOLATION OF THE MANUFACTURES IS LISTING. THERE ARE FEEDERS FROM THIS SERVICE THAT RUNS TO THE ADJACENT PANEL WHICH IS AN OTHER ALL IN ONE SERVICE DISCONNECT (ALL IN ONE (B)) WITH A BLANK COVER AT THE METER SOCKET. THE FEEDERS ENTER THE BOTTOM THE PANEL (B) ON THE INTERIOR OF THE PREMISE SIDE AND THEN THEY ENTER THE UTILITY SIDE UNPROTECTED BY WAY OF THE SIDE WALL UP INTO THE METER SOCKET. THERE ARE ENERGIZED FEEDERS ON THE PREMISE SIDE OF THE PANEL. THE OVERHEAD FEEDERS FROM THE SECONDARY RISER RUN OVER THE TOP OF THE ROOF AND ARE NOT CODE COMPLAINT. THESE FEEDERS FEED A PANEL MOUNTED ON A DETACHED QUAD PLEX. THIS MODIFICATION IS NOT SAFE AND NOT CODE COMPLIANT, TEP DID SECURE THE PREMISE SIDE OF THE MAIN DISCONNECT (A). |