Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2018 | INSP - INITIAL CODE ENFORCMENT | Approved | INOPERABLE WINDOW IN THE MAIN BEDROOM WINDOW LOCATED IN THE BATHROOM IS BROKEN. FRAMING IS DETERIORATED AND RUSTED INOPERABLE WINDOW IN THE LIVING ROOM DINING ROOM WINOW SCREEN IS NOT PROPERLY SECURED FRONT DOOR DOES NOT SEAL PROPERLY ELECTRICAL CIRCUIT FOR THE STOVE IS NOT SECURED AND NOT PROTECTED FROM DAMAGE KITCHEN STOVE FAN IS INOPERABLE HALL LIGHT IS INOPERABLE SMOKE DETECTOR IN INOPERABLE INPROPER ELECTRICAL RUN IN THE APPLIANCE ROOM, NOT SECURED TO THE WALL, EXCESS CONDUIT IS HANGING REAR DOOR DOES NOT SHUT PROPERLY. FRAMING AROUND THE REAR DOOR IS DETERIORATED AND NOT PROPERLY SEALED REAR DOOR LIGHT FIXTURE IS INOPERABLE COOLER IS EXTREMELY DETERIORATED WITH EXCESSIVE RUST AND CALCIUM BUILD UP. ELECTRICAL PANELS DETERIORATED AND HAVE EXCESSIVE RUST INSUFFICIENT SIZE OF SHUT OFF BREAKER FOR 4652 MISSING PUNCH OUTS ON PANEL AND DEAD FRONT. ON PANEL MISSING A DEAD FRONT GROUND IS BROKEN FROM THE WATER PIPING. NO EVIDENCE OF GROUNDING RODS UNSECURED CONDUIT COMING FROM THE PANELS PANELS LACK ALL LABELING UNKNOW BREAKERS IN THE PANELS |