Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
Case Number - T18DV02722
Inspection Description - INSP - FOLLOW UP CODE ENFORCE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | The unit is vacant and secured. The electrician showed and check the unit and all is OK. The contractor Net Electric Company, INC sent a letter stating all is OK. There is no other damage and the water has been extracted and all is dry at this time. The unit will be cleaned. At this time the case will be closed. Violation Abated, Close Case. RV. | |
05/13/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | The contractor called that was working on the fire system and the system has been repaired and back on line. The fire supervisor has been called at communication and advised that the fire system is back on line and the sprinkler head will be replaced on Tuesday. They are looking for a part where the Tee was broken in the PVC piping. RV. | |
05/12/2018 | INSP - FOLLOW UP CODE ENFORCE | Approved | The building went into fire watch due to the repair was not holding pressure and started to leak at 10:00 PM. T.F.D. was notified that the fire watch was going to start. The company doing the work will check it tomorrow and try and get back on line. They will call if back on line. RV. |