Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2018 | INSP - INITIAL CODE ENFORCMENT | Approved | EMERGENCY CALL OUT BY TFD: MAIN DISCONNECT HAS BOTH FEEDERS WITH BURNT AND CRACKED INSULATION AT THE TERMINATION POINT OF THE MAIN BREAKER, THE HOT CONDUCTOR AND NUETRAL LOOK LIKE THERE TOUCHING AT THE DAMAGED INSULATION AREA. THIS MAIN DISCONNECT HAS NO MAIN BREAKER, THE MAIN BREAKER TERMINAL LUG IS DISCOLORED, SIGNS OF OVER HEATING. THERE IS INTERNAL DAMAGE TO THE MAIN BREAKER DUEO OVER HEATING. THERE ARE 10 OTHER CIRCUIT BREAKERS WHICH EXCEED MAXIMUN ALLOWED. THERE ARE OTHER COE VIOLATIONS IN THE PANEL. THE TENANT CALLED TFD DUE TO A BURNING SMELL FROM THE MAIN DISCONNECT. TEP ON SITE AND DID DISCONNECT POWER. PERMIT REQUIRED FOR REPAIRS OR AN UPGRADE, THE DWELLING WAS CONDEMNED. |