Case: T18DV01282
Case Details
Entered Date:
03/12/2018
Applicant:
WARING ROBERT P
Description:
ELECTRICAL FEEDERS BURNT
Outstanding Inspections
Case Number: T18DV01282
Case Status: COMPLIAN
Case Description: CONDEMNATION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| EMERGENCY CALL OUT | None | Not Inspected |
Completed Inspections
Case Status: COMPLIAN
Case Number: T18DV01282
Case Description: CONDEMNATION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2018 | INSP - INITIAL CODE ENFORCMENT | VALDEZ | Approved | EMERGENCY CALL OUT BY TFD: MAIN DISCONNECT HAS BOTH FEEDERS WITH BURNT AND CRACKED INSULATION AT THE TERMINATION POINT OF THE MAIN BREAKER, THE HOT CONDUCTOR AND NUETRAL LOOK LIKE THERE TOUCHING AT THE DAMAGED INSULATION AREA. THIS MAIN DISCONNECT HAS NO MAIN BREAKER, THE MAIN BREAKER TERMINAL LUG IS DISCOLORED, SIGNS OF OVER HEATING. THERE IS INTERNAL DAMAGE TO THE MAIN BREAKER DUEO OVER HEATING. THERE ARE 10 OTHER CIRCUIT BREAKERS WHICH EXCEED MAXIMUN ALLOWED. THERE ARE OTHER COE VIOLATIONS IN THE PANEL. THE TENANT CALLED TFD DUE TO A BURNING SMELL FROM THE MAIN DISCONNECT. TEP ON SITE AND DID DISCONNECT POWER. PERMIT REQUIRED FOR REPAIRS OR AN UPGRADE, THE DWELLING WAS CONDEMNED. |
| 03/13/2018 | INSP - FOLLOW UP CODE ENFORCE | VALDEZ | Approved | DOCUMENTS AND PHOTOS IN SIRE . CLOSE CASE |
Completed Activity Special Conditions
Case Description - CONDEMNATION
Case Number - T18DV01282
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 3
| Date | Name |
| 03/12/2018 | CONTACTED BY PHONE |
| 03/12/2018 | CONTACTED IN PERSON |
| 03/12/2018 | NOTICE AND ORDER ISSUED |