Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/08/2018 | INSP - INITIAL CODE ENFORCMENT | Approved | Numerous Electrical Hazards: Overhead Service Entrance conductors were burnt. Found excessive loads at the main 200 amp service. Two 60 amp breakers were feeding 15 additional units. One was feeding the north side with 50 amp conductors underground to a 100 amp back feed breaker for six units. There is two sub panels with several conduits across the back of the structure and across the roof. Most conduits are filled with no derating applied. Junction boxes are undersized on the structure and roof. Panel labeling is not clear as to circuits served. The south side was feed over the roof then underground for the duplex in front and six unit plus an office with 60 amp conductors to a panel with no main breaker. An 80 amp breaker feed the duplex and a 50 amp breaker feed the rear units and office with 50 amp conductors across the roof and then underground. The rear panel had no main breaker. The 90 amp breaker feed goes across the roof in and out of PVC conduits exposing conductors and splices. The individual unit have exposed conductors undersized from the main conductors down to the internal sub panels. Panel labeling is not clear as to circuits served. Most of the units have surface mounted conduits to junction boxes and devices. Wall mounted baseboard heaters have been installed in many unit that are not code compliant with installation or load applications for circuits. There is exposed conductors on the inside of a bathroom/linen cupboard for a receptacle. GFCI's are not present for bathrooms and kitchens as per codes at all units. Ceiling fans are being supported by boxes not rated for the weight or application. There is grounded receptacles on non-grounded circuits. There is no record of permits for these modifications to the units. Power strips and extension cords in use were lack of receptacles available. At the rear of the property is an outdoor LED light fixture installed after 05/2016 per google view. No permit in the system. |