Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE - FINAL
Permit Number - T18CM10049
Inspection Description - FIRE - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2019 | FIRE - FINAL | Partial Approval | only waiting on annual sprink insp report | |
10/25/2019 | FIRE - FINAL | Approved | ||
09/26/2019 | FIRE - FINAL | Correction Required | see previous notes under fire final. these are more notes in addition to those. still needs a fire final inspection. -riser brace needs repair. -spare head box missing or unable to find. -label inspectors test valve ceiling tile. -one head is piped prior to the flow switch. it needs to be after the flow switch. PER PHONE CONVERSATION OKAY FOR TCO 10/16/19 KR |
|
09/25/2019 | FIRE - FINAL | Correction Required | These are notes only from the sprinkler walk. Still needs full fire final inspection. -need annual sprink inspection, correct deficiencies. -need 5yr internal check valve inspection, correct deficiencies. -FDC sign above connections with address. -knox box x 2 with keys, front and rear of bldg. -electrical room sign on door. -FACP sign on door. -missing trim on some sprink heads. -all sprink heads need to be free of mud/paint. APPROVED TO MOVE IN EQUIPMENT. |