Permit: T18CM10049

Parcel: 12201024J


Addresses:

3920 E GRANT RD

Inspection Status: Partial Approval

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
10/25/2019 FIRE - FINAL Partial Approval only waiting on annual sprink insp report
10/25/2019 FIRE - FINAL Approved
09/26/2019 FIRE - FINAL Correction Required see previous notes under fire final. these are more notes in addition to those. still needs a fire final inspection.
-riser brace needs repair.
-spare head box missing or unable to find.
-label inspectors test valve ceiling tile.
-one head is piped prior to the flow switch. it needs to be after the flow switch.
PER PHONE CONVERSATION OKAY FOR TCO 10/16/19 KR
09/25/2019 FIRE - FINAL Correction Required These are notes only from the sprinkler walk. Still needs full fire final inspection.
-need annual sprink inspection, correct deficiencies.
-need 5yr internal check valve inspection, correct deficiencies.
-FDC sign above connections with address.
-knox box x 2 with keys, front and rear of bldg.
-electrical room sign on door.
-FACP sign on door.
-missing trim on some sprink heads.
-all sprink heads need to be free of mud/paint.
APPROVED TO MOVE IN EQUIPMENT.