Permit: T18CM10049

Parcel: 12201024J


Addresses:

3920 E GRANT RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
08/28/2019 PLUMBING - ROUGH, SOIL Approved Perimeter deck drain rough ok to backfill
05/09/2019 PLUMBING - ROUGH, SOIL Partial Approval Sewer tie in.
05/06/2019 PLUMBING - ROUGH, SOIL Partial Approval Steam room and sauna
04/25/2019 PLUMBING - ROUGH, SOIL Partial Approval Picked up RFI from PE regarding WC arm sizing.
changed to PA due to other inspections
04/23/2019 PLUMBING - ROUGH, SOIL Denied 1- The approved plans call for all water closet trap arms to be full size 4 inch.
2- Shall remove and replace the 6 x 4 fernco reducer coupling and provide a shielded mission specialty coupling within the structure.