Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2019 | FRAMING | Approved | ||
| 11/20/2019 | FRAMING | Cancelled | per phone call with customer. | |
| 09/23/2019 | FRAMING | Not ready for Inspection | Should be scheduled with intermediates | |
| 08/14/2019 | FRAMING | Not ready for Inspection | Partial inspection of roof framing and exterior walls only at this time. 2x6 rafters that are full length over brick portion are over-spanned per IRC Table R802.4.1(1). 1-Install knee wall to roof below over rafter at existing wall near mid-span. 2-Some pitch cuts are incorrect at ridge; install pressure blocking on both sides of these at the ridge. Reschedule with intermediates. |