Permit: T18CM09984

Parcel: 140420120


Addresses:

7081 S PLUMER AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/03/2020 PLUMBING - INTERMEDIATE Approved Approved
08/12/2020 PLUMBING - INTERMEDIATE Partial Approval Partial, Agricultural lab (Drain, waste, Vent & Potable water lines) ok to proceed.
07/31/2020 PLUMBING - INTERMEDIATE Partial Approval Partial, Shell space rooms 106 & 108 water fountain and sink Inspected.
07/24/2020 PLUMBING - INTERMEDIATE Partial Approval partial
1- DWV system and overhead and in wall domestic water distribution is okay to cover for the East wing only.
07/08/2020 PLUMBING - INTERMEDIATE Denied denied
1- Shall provide a minimum of 10 feet water head test on the DWV system.
2- Can not connect a drain into the vent to the water closet. Shall wet vent the Urinal.
3- Shall provide Mission Specialty couplings when making a transition of dissimilar materials..