Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T18CM09984
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/03/2020 | PLUMBING - INTERMEDIATE | Approved | Approved | |
08/12/2020 | PLUMBING - INTERMEDIATE | Partial Approval | Partial, Agricultural lab (Drain, waste, Vent & Potable water lines) ok to proceed. | |
07/31/2020 | PLUMBING - INTERMEDIATE | Partial Approval | Partial, Shell space rooms 106 & 108 water fountain and sink Inspected. | |
07/24/2020 | PLUMBING - INTERMEDIATE | Partial Approval | partial 1- DWV system and overhead and in wall domestic water distribution is okay to cover for the East wing only. |
|
07/08/2020 | PLUMBING - INTERMEDIATE | Denied | denied 1- Shall provide a minimum of 10 feet water head test on the DWV system. 2- Can not connect a drain into the vent to the water closet. Shall wet vent the Urinal. 3- Shall provide Mission Specialty couplings when making a transition of dissimilar materials.. |