Inspection History Details
Inspection Status: Approved
Inspection History: FIRE INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2019 | FIRE INTERMEDIATE | Approved | ||
| 07/10/2019 | FIRE INTERMEDIATE | Partial Approval | Need to have a 5 year inspection performed on the fire riser Need to have the water motor gong removed and a bell added at the back of the building For TCO to stock, need water flow and tamper monitored off site by the fire alarm system Fire Extinquishers shall be located every 75 feet Need the address on the building 15" numbers Need to order 2 KNOX FDC caps and have the FDC flushed prior to installation KNOX boxs needed for the front and back location Need to obtain FACP, RISER ROOM signs |
|
| 07/10/2019 | FIRE INTERMEDIATE | Partial Approval | Tested the fire sprinkler water flow and tamper switch. Cmfirmed that they are sending signals to offsite monitoring via cellular dialer |