Permit: T18CM09810

Parcel: 121050220


Addresses:

5548 E GRANT RD

Inspection Status: Approved

Inspection History: FIRE INTERMEDIATE

Date Description Inspector Results Comments
07/23/2019 FIRE INTERMEDIATE Approved
07/10/2019 FIRE INTERMEDIATE Partial Approval Need to have a 5 year inspection performed on the fire riser
Need to have the water motor gong removed and a bell added at the back of the building
For TCO to stock, need water flow and tamper monitored off site by the fire alarm system
Fire Extinquishers shall be located every 75 feet
Need the address on the building 15" numbers
Need to order 2 KNOX FDC caps and have the FDC flushed prior to installation
KNOX boxs needed for the front and back location
Need to obtain FACP, RISER ROOM signs
07/10/2019 FIRE INTERMEDIATE Partial Approval Tested the fire sprinkler water flow and tamper switch. Cmfirmed that they are sending signals to offsite monitoring via cellular dialer