Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T18CM09086
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/18/2020 | FIRE - FINAL | Approved | ||
02/10/2020 | FIRE - FINAL | Partial Approval | -Post address on marquee sign so it is readable from the street -Maintain clear access to electrical panels, shelving in front of panel at laundry room -complete sprinkler and alarm permit inspections |
|
01/22/2020 | FIRE - FINAL | Denied | -Post address on building so it is visible form the street, per Pima County Address codes -Post "Riser Room", "FDC" and "FACP" signs -Provide FDC Knox plug -Provide and mount Knox box next to riser room -Emergency lights on north side of home did not operate -Mount fire extinguisher on north side of home -Label breakers in electrical panels -Complete sprinkler and fire alarm inspections. |