Permit: T18CM08485

Parcel: 141366820


Addresses:

7401 S WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T18CM08485

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/28/2020 PLUMBING - INTERMEDIATE Approved
12/23/2019 PLUMBING - INTERMEDIATE Partial Approval no inspection done at this time.
12/20/2019 PLUMBING - INTERMEDIATE Partial Approval Area A in wall Potable water ok.
12/17/2019 PLUMBING - INTERMEDIATE Partial Approval 1- DWV system is okay in Area A only.
12/05/2019 PLUMBING - INTERMEDIATE Partial Approval All Potable water lines in Area B under test and Approved at 100PSI.
12/04/2019 PLUMBING - INTERMEDIATE Partial Approval Area B Potable water air test Approved for Janitors closet to decontamination room. Riser room to mechanical room, & 140 degree circuit from mechanical room to kitchen. Ok to insulate these lines and strap where necessary.
11/22/2019 PLUMBING - INTERMEDIATE Partial Approval Cast iron DWV in walls for Area B under test and Approved, stopped inspection at Grid Line J.0.