Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T18CM08485
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/28/2020 | PLUMBING - ROUGH, SOIL | Approved | ||
02/21/2020 | PLUMBING - ROUGH, SOIL | Partial Approval | waste and Vent for decontamination tank inspected, under test and ok to backfill. Grease waste line and Interceptor under test and ok to backfill. | |
02/07/2020 | PLUMBING - ROUGH, SOIL | Partial Approval | REOPENED FOR REINSPECTION | |
07/19/2019 | PLUMBING - ROUGH, SOIL | Partial Approval | Area A, ok to backfill. Also all corrections in Area B from inspection on 07/12/19 have been done and are acceptable. THIS WAS A SAME DAY INSPECTION. $165 FEE HAS BEEN ASSESSED, BUT NOT YET PAID. |
|
07/12/2019 | PLUMBING - ROUGH, SOIL | Partial Approval | Area B, excluding riser room, ok to backfill except as follows : 1. Need to get approval from engineer to use 3" trap arms at all water closets, isometric drawings show 4", backfill at own risk. 2. Need to fix and retest 2 locations that have leaks on grease waste at 2" fitting and 4" fitting 3. Need to extend trap arm length at floor sink in Room 238 and retest. |