Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T18CM08485
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2020 | ELECTRIC - INTERMEDIATE | Approved | ||
02/28/2020 | ELECTRIC - INTERMEDIATE | Partial Approval | Electrical Conduits in CMU wall for generator inspected. | |
02/21/2020 | ELECTRIC - INTERMEDIATE | Partial Approval | Line termination to RTU1 inspected and approved. | |
02/19/2020 | ELECTRIC - INTERMEDIATE | Partial Approval | Line Termination for RTU’s #2 & 3 Inspected. | |
02/05/2020 | ELECTRIC - INTERMEDIATE | Partial Approval | Inspection of 1600AMP 480/277V SES Note: plans call for 5 Parallel #600KCMIL CU Conductors, Contractor substituted with 5- #750KCMIL AL Conductors. Inspection from SES to MSA And to 4 AutomaticTransferSwitches for Critical and Life safety branch panels inspected and per plan. Provide Clearance to TEP ECO. | |
01/14/2020 | ELECTRIC - INTERMEDIATE | Partial Approval | Inspection of 10-480/277V>120/208V Transformers for Electrical rooms A & B Panels Approved. | |
12/27/2019 | ELECTRIC - INTERMEDIATE | Partial Approval | Area A CT, X-Ray, and exam rooms Electrical in walls ok. | |
12/11/2019 | ELECTRIC - INTERMEDIATE | Partial Approval | Area B Operating room, Electrical in walls from Isolated system ok. Also Inspected Putty packs at area B, where Fire Assembly Boxes required Fire barrier. | |
12/09/2019 | ELECTRIC - INTERMEDIATE | Partial Approval | Two Trauma rooms and Isolation exam room area B ok. | |
12/02/2019 | ELECTRIC - INTERMEDIATE | Partial Approval | 1- MC cables and metal boxes are okay to cover in walls for first floor Mosu rooms and Procedures rooms only. | |
11/21/2019 | ELECTRIC - INTERMEDIATE | Partial Approval | Electrical in walls for Area B from GL (J.0-K.0/3.0-6.0). | |
11/18/2019 | ELECTRIC - INTERMEDIATE | Partial Approval | Electrical in Walls ok for Phase B from GL-L.0- 2.0 except Operating Room, I.T Room, & North Corridor. |