Permit: T18CM08485

Parcel: 141366820


Addresses:

7401 S WILMOT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T18CM08485

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/05/2020 ELECTRIC - INTERMEDIATE Approved
02/28/2020 ELECTRIC - INTERMEDIATE Partial Approval Electrical Conduits in CMU wall for generator inspected.
02/21/2020 ELECTRIC - INTERMEDIATE Partial Approval Line termination to RTU1 inspected and approved.
02/19/2020 ELECTRIC - INTERMEDIATE Partial Approval Line Termination for RTU’s #2 & 3 Inspected.
02/05/2020 ELECTRIC - INTERMEDIATE Partial Approval Inspection of 1600AMP 480/277V SES Note: plans call for 5 Parallel #600KCMIL CU Conductors, Contractor substituted with 5- #750KCMIL AL Conductors. Inspection from SES to MSA And to 4 AutomaticTransferSwitches for Critical and Life safety branch panels inspected and per plan. Provide Clearance to TEP ECO.
01/14/2020 ELECTRIC - INTERMEDIATE Partial Approval Inspection of 10-480/277V>120/208V Transformers for Electrical rooms A & B Panels Approved.
12/27/2019 ELECTRIC - INTERMEDIATE Partial Approval Area A CT, X-Ray, and exam rooms Electrical in walls ok.
12/11/2019 ELECTRIC - INTERMEDIATE Partial Approval Area B Operating room, Electrical in walls from Isolated system ok. Also Inspected Putty packs at area B, where Fire Assembly Boxes required Fire barrier.
12/09/2019 ELECTRIC - INTERMEDIATE Partial Approval Two Trauma rooms and Isolation exam room area B ok.
12/02/2019 ELECTRIC - INTERMEDIATE Partial Approval 1- MC cables and metal boxes are okay to cover in walls for first floor Mosu rooms and Procedures rooms only.
11/21/2019 ELECTRIC - INTERMEDIATE Partial Approval Electrical in walls for Area B from GL (J.0-K.0/3.0-6.0).
11/18/2019 ELECTRIC - INTERMEDIATE Partial Approval Electrical in Walls ok for Phase B from GL-L.0- 2.0 except Operating Room, I.T Room, & North Corridor.