Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T18CM08177
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2019 | ELECTRIC - UNDERGROUND | Approved | ||
05/16/2019 | ELECTRIC - UNDERGROUND | Partial Approval | 3/4" Conduits, 2" conduits, 3" Conduits Approved, ok to back fill South End of Bldg #2. | |
05/13/2019 | ELECTRIC - UNDERGROUND | Partial Approval | (3-4" PVC Conduits from Existing building #3 CT Cabinet to location of new SES). (4-4" PVC Conduits from Location of new SES to South end of building #2). (1-3" PVC conduit from building #1 to building #2 for Data/Communication). (1-3" PVC conduit from building #1 to building #2 for Data/Communication). |
|
05/10/2019 | ELECTRIC - UNDERGROUND | Partial Approval | Work to be done incomplete upon arrival | |
05/07/2019 | ELECTRIC - UNDERGROUND | Partial Approval | 7-4" Conduits from Existing Transformer to Location of new SES. OK to backfill trench near Transformer. | |
04/09/2019 | ELECTRIC - UNDERGROUND | Partial Approval | Utility conduits under slab ok |