Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
Permit Number - T18CM08138
Inspection Description - BUILDING ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2019 | BUILDING ABOVE CEILING | Approved | ||
06/07/2019 | BUILDING ABOVE CEILING | Partial Approval | OK to cover first floor lobby west side only if work needs to get completed this weekend, otherwise would prefer to see it Monday 100% complete. Before covering finish work on lights, still being installed at time of inspection. Seismic wiring needs to be completed mainly on the far west end. Make sure mechanical branches are to there openings. One branch arm is not reaching it’s opening. Make sure mechanical dampers are accessible. |