Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/10/2019 |
BUILDING - FINAL |
|
Approved |
ALL INSPECTIONS COMPLETED AND CERTIFICATES TURNED IN. DEBRIS CLEARED. (OK'S PER PHONE CONVERSATION WITH MIKE HASSAN) |
| 07/03/2019 |
BUILDING - FINAL |
|
Partial Approval |
not much change from previous inspection. Still OK for TCO for stocking fixturing and moving in furniture only. To change TCO status or to get a full C of O need engineering’s approval, need special inspection paperwork submitted, and need water chlorination report completed and submitted. Need building clear and free of debris. Left voicemail explaining the situation for contact number left on Message. |
| 06/24/2019 |
BUILDING - FINAL |
|
Partial Approval |
OK for TCO for stocking, fixturing, and moving in furniture. For full approval still pending, fire department approval, engineering’s approval, water chlorination report and any pending special inspections. Also need address visible on Irvington side and site free and clear of debris. |
| 06/11/2019 |
BUILDING - FINAL |
|
Not ready for Inspection |
pending completion of site work, engineering and fire departments approval, ADA signage and dispensers. Special inspection paperwork. Also top ladder steps for roof access do not seem to have enough projection, 3 inches is a typical minimum, this could be a safety issue for maintenance workers. |