Inspection Status: Passed
Inspection History: COT - FCON - Fire - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 03/15/2019 |
COT - FCON - Fire - Final |
CBASALDUA |
Approved |
Entered by CBASALD1 - |
| 02/08/2019 |
COT - FCON - Fire - Final |
jvincent |
Denied |
Entered by JVINCEN1 - 1. repair sprinkler heads. some are bent. some are too low below the tiles or too high.
2. provide key for knox box.
3. annual and 5yr inspection report for fire alarm.
4. annual inspection report for fire alarm.
5. AES radio was not permitted. replace with cellular dialer and phone line.
6. power strip set up next to fire alarm panel for transformer needs to be corrected and locked.
7. suite number rear doors.
8. flush FDC's, AHJ to witness.
9. add supports to arm overs that were added.
10. knox FDC plugs needed after flush. Have on site during flush so we can install immediatley after flush.
11. mount extinguishers.
Contact: Jay Post 310-1611 |