Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T18CM07191

Parcel: 112052790

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/14/2018 PLUMBING - GAS PRESSURE TEST Approved
09/13/2018 PLUMBING - GAS PRESSURE TEST Denied GAS PRESSURE TEST IS 4LB, WHICH NEEDS TO BE AT LEAST 10LBS FOR 15 TO 30 MINS.