Permit: T18CM06772

Parcel: 10825287A


Addresses:

2404 E RIVER RD 01

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
01/31/2019 FIRE - FINAL Approved
01/22/2019 FIRE - FINAL Partial Approval -need annual sprink inspection report
-need annual alarm inspection report. cintas to obtain permit for change of monitoring. will need to conduct an acceptance test when cintas calls in permit.
-knox box has been ordered. will call us when mounted.
contact: alex 258-8232
OK to move in furniture.
01/18/2019 FIRE - FINAL Partial Approval -need annual sprink inspection report
-need annual alarm inspection report
-will mount extinguisher
-order/mount FD knox box, provide key.
-label door "FACP"
-label door "fire riser room"
alex 258-8232