Permit: T18CM06725

Parcel: 107130310


Addresses:

2736 N STONE AV #02

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/23/2019 ELECTRIC - ABOVE CEILING Approved
01/22/2019 ELECTRIC - ABOVE CEILING Cancelled Cancel by contractor
01/16/2019 ELECTRIC - ABOVE CEILING Denied For all units, missing ground screws secure conduit 12 inches from all boxes, check boxes for box fill
01/10/2019 ELECTRIC - ABOVE CEILING Not ready for Inspection 1- Work is incomplete.
01/08/2019 ELECTRIC - ABOVE CEILING Denied 1- Shall hard wire the smoke detectors as per approved plans.
10/30/2018 ELECTRIC - ABOVE CEILING Not ready for Inspection Some electrical conduit not secured to wall, some metal boxes not grounded, some bathroom vent fans not wired.