Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T18CM06723

Parcel: 107130300


Addresses:

2740 N STONE AV #02

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/23/2019 ELECTRIC - ABOVE CEILING Approved
01/22/2019 ELECTRIC - ABOVE CEILING Cancelled Cancel by contractor
01/16/2019 ELECTRIC - ABOVE CEILING Denied For all units, missing ground screws secure conduit 12 inches from all boxes, check boxes for box fill
01/10/2019 ELECTRIC - ABOVE CEILING Not ready for Inspection
01/10/2019 ELECTRIC - ABOVE CEILING Not ready for Inspection 1- Work is incomplete
01/08/2019 ELECTRIC - ABOVE CEILING Denied 1- Shall hard wire the smoke detectors as per the approved plans.
10/30/2018 ELECTRIC - ABOVE CEILING Not ready for Inspection Some bathroom fans not wired, some conduit is terminated without bushing.